O&I Hearing: Corrosion, Collapse, and Clean-Up: Examining the Potomac Interceptor Collapse
John Joyce, Yvette Clarke, Guthrie, Palone, Jessica Kramer, Francis Pera, Edward Wenshoff, David Gaddis, Tom Neltner, Balderson, Tonko, Allen, Harshberger, Cortez, Weber, Palmer
Hearing
The Incident and Immediate Response
- On January 19, 2026, a 72-inch segment of the 54-mile Potomac Interceptor, a sanitary sewer system operating since the 1960s, collapsed.
- The collapse resulted in an estimated 240 million gallons of raw, untreated sewage overflowing into the Potomac River and adjacent land.
- The spill was identified as one of the worst sanitary sewer overflows (SSOs) in U.S. history.
- Emergency response efforts were coordinated by D.C. Water, the EPA, the U.S. Army Corps of Engineers (USACE), and the National Park Service (NPS).
- A temporary bypass system was constructed and became operational by January 24, 2026, using a section of the Chesapeake and Ohio (C&O) Canal to divert flow around the collapse.
- Full wastewater flow was restored to the Interceptor on March 14, 2026, one week ahead of the projected schedule.
- Federal remediation activities were declared complete on May 6, 2026, with the exception of specific soil removal within the C&O Canal prism.
- The USACE installed a stormwater diversion system using poly liners and sandbags to prevent further contamination during wet weather.
- Remediation involved the removal of contaminated soil in 3-inch layers, scrubbing historic masonry locks, and replanting vegetation.
Infrastructure Vulnerability and Aging Assets
- D.C. Water confirmed awareness of the specific pipe segment's vulnerability as far back as 2017–2018, placing it on their Capital Improvement Program (CIP) list for rehabilitation.
- Permitting applications with the National Park Service (NPS) were submitted in 2018 but were not finalized at the time of the collapse.
- D.C. Water cited the permitting process, including required environmental impact assessments that were restarted due to design changes, as a primary factor in the delay.
- The collapse was exacerbated by the presence of boulders weighing approximately 18 tons (equivalent to 10 passenger vehicles) situated atop the pipe.
- These boulders obstructed flow and contributed to structural stress but were located outside the pipe and were not detectable via standard internal CCTV inspections.
- D.C. Water CEO David Gaddis stated that the agency was not previously aware of the dangerous potential of these specific external boulders.
- The hearing highlighted a nationwide infrastructure crisis with a $1.2 trillion funding gap for water system repairs and upgrades.
- The EPA's most recent needs assessment indicates a massive shortfall, with $110 billion specifically required for aging sewer repairs.
Jurisdictional and Regulatory Challenges
- Permits for the pipe repair were delayed for eight years due to the NPS's environmental review process for the C&O Canal National Historical Park.
- NPS Acting Superintendent Edward Wenshoff noted that while emergency declarations allow for verbal authorizations to proceed, standard construction permits for utilities on park land can take 6 to 12 months.
- D.C. Water requested fast-track permits in 2018 for corrosion repairs, which were delayed by the need for new environmental assessments following plan modifications.
- Litigation filed by the Department of Justice against D.C. Water and the District of Columbia is pending regarding Clean Water Act violations.
- EPA Assistant Administrator Jessica Kramer declined to discuss the cause of the collapse due to the ongoing litigation.
- The hearing exposed disagreements regarding the speed of the response and the role of the federal government.
- Representative Clark and Mr. Palmer questioned whether the NPS and D.C. Water could have expedited permits to prevent the disaster.
- D.C. Water testified that they did not have a role in urging the District of Columbia to declare a public emergency until February 18, 2026, despite knowing of the risk for years.
Drinking Water Safety and Secondary Risks
- The collapse did not threaten the safety of the Washington, D.C. drinking water supply because the overflow occurred downstream of the Washington Aqueduct's primary intake at Great Falls.
- The primary intake is located approximately 5.8 miles north of the collapse site.
- The secondary intake at Little Falls, located less than 4 miles downstream, was closed for the 2025-2026 low season.
- Witnesses noted that a collapse occurring further upstream could have contaminated the drinking water supply.
- The current reservoir storage capacity at the Washington Aqueduct provides approximately 12 hours of water supply if intakes are closed.
- A feasibility study for a secondary water source is underway, though it faces funding and timeline constraints.
Budgetary and Political Context
- Committee members criticized the Trump Administration's FY27 budget proposal, which calls for an 86% cut to the Drinking Water State Revolving Fund and a 90% cut to the Clean Water State Revolving Fund.
- Critics argued these cuts would hinder the ability of water systems to perform necessary preventative maintenance and upgrades.
- The administration's budget was contrasted with reported allocations for the White House East Wing demolition and a $1.8 billion slush fund.
- President Trump's public comments following the collapse accused political opponents of causing the incident, which witnesses and committee members characterized as unhelpful and lacking basis.
- EPA Assistant Administrator Kramer clarified that the collapse was due to aging infrastructure and asset management challenges, not political action.
Future Recommendations and Actions
- D.C. Water announced it has identified three additional high-risk segments of the 54-mile pipe that require urgent attention.
- The agency plans to mobilize repairs on these segments within 30 days and is seeking changes to the permitting process to allow for faster action.
- Federal agencies and utilities are focusing on "asset management" strategies to identify vulnerabilities before failures occur.
- Recommended improvements include using ground-penetrating radar to detect external obstructions (like boulders) rather than relying solely on internal inspections.
- Unleaded Kids Director Tom Neltner emphasized the need for increased federal funding and enforcement to prevent future sanitary sewer overflows.
- He noted that while 23,000 to 75,000 SSOs occur annually, the majority go uncounted, causing significant public health and environmental risks.